The table below lists the wire Characteristics for different gauges of
the American Wire Gauge [AWG]. The American Wire Gauge provides a
means of specifying wire diameters. For each different AWG [wire size]
the table provides the Diameter [in mils], the resistance per 1000 foot,
the current carrying capability [Ampacity], and Pounds per Foot [number
of feet required to weigh 1 pound].
The AWG is based upon a constant ratio of cross-section between wires of successive gage numbers.
Read the notes below the table to
determine how the Ampacity was derived. The larger the AWG number, the
smaller diameter wire. The table is based on an ambient temperature of
25oC. Some of the standard wire sizes used in a number of
Interface Buses [for data lines] are #22AWG, #24AWG, #26AWG, and 30AWG. A
listing of Electronic bus standards are located on the Buses page. Another table near the bottom of the
page provides copper current carrying ability [Ampacity] for Teflon
insulated wire. Conductor size is based one or more of the following
considerations:
Current carrying capacity [inducing a rise in wire temperature, in
high-voltage lines], Short circuit current, or Voltage drop [long low
voltage lines].
AWG | Diam. (mils) | Circular mils | Ohms/1000ft | Current Carrying | Fusing Current | Feet per Pound |
0000 | 460 | 212000 | 0.050 | - | - | 1.56 |
000 | 410 | 168000 | 0.063 | - | - | 1.96 |
00 | 365 | 133000 | 0.077 | - | - | 2.4826 |
0 | 324.85 | 105531 | 0.096 | - | - | 3.1305 |
1 | 289.3 | 83694 | 0.1264 | 119.6 | - | 3.947 |
2 | 257.6 | 66358 | 0.1593 | 94.8 | - | 4.977 |
3 | 229.4 | 52624 | 0.2009 | 75.2 | - | 6.276 |
4 | 204.3 | 41738 | 0.2533 | 59.6 | - | 7.914 |
5 | 181.9 | 33088 | 0.3915 | 47.3 | - | 9.980 |
6 | 162 | 26244 | 0.4028 | 37.5 | 668 | 12.58 |
7 | 144.3 | 20822 | 0.5080 | 29.7 | 561 | 15.87 |
8 | 128.5 | 16512 | 0.6405 | 23.6 | 472 | 20.01 |
9 | 114.4 | 13087 | 0.8077 | 18.7 | 396 | 25.23 |
10 | 101.9 | 10384 | 1.018 | 14.8 | 333 | 31.82 |
11 | 90.7 | 8226 | 1.284 | 11.8 | 280 | 40.12 |
12 | 80.8 | 6529 | 1.619 | 9.33 | 235 | 50.59 |
13 | 72.0 | 5184 | 2.042 | 7.40 | 197 | 63.80 |
14 | 64.1 | 4109 | 2.575 | 5.87 | 166 | 80.44 |
15 | 57.1 | 3260 | 3.247 | 4.65 | 140 | 101.4 |
16 | 50.8 | 2581 | 4.094 | 3.69 | 117 | 127.9 |
17 | 45.3 | 2052 | 5.163 | 2.93 | 98.4 | 161.3 |
18 | 40.3 | 1624 | 6.510 | 2.32 | 82.9 | 203.4 |
19 | 35.9 | 1289 | 8.210 | 1.84 | 69.7 | 256.5 |
20 | 32.0 | 1024 | 10.35 | 1.46 | 58.4 | 323.4 |
21 | 28.5 | 812 | 13.05 | 1.16 | - | 407.8 |
22 | 25.3 | 640 | 16.46 | .918 | 41.2 | 514.12 |
23 | 22.6 | 511 | 20.76 | .728 | - | 648.4 |
24 | 20.1 | 404 | 26.17 | .577 | 29.2 | 817.7 |
25 | 17.9 | 320 | 33.0 | .458 | - | 1031 |
26 | 15.9 | 253 | 41.62 | .363 | 20.5 | 1300 |
27 | 14.2 | 202 | 52.48 | .288 | - | 1639 |
28 | 12.6 | 159 | 66.17 | .228 | 14.4 | 2067 |
29 | 11.3 | 128 | 83.44 | .181 | - | 2607 |
30 | 10.0 | 100 | 105.2 | .144 | 10.2 | 3287 |
31 | 8.9 | 79 | 132.7 | .114 | - | 4145 |
32 | 8.0 | 64 | 167.3 | .090 | - | 5227 |
33 | 7.1 | 50.125 | 211.0 | .072 | - | 6591 |
34 | 6.3 | 39.75 | 266.0 | .057 | 5.12 | 8310 |
35 | 5.6 | 31.5 | 335 | .045 | 4.28 | 10480 |
36 | 5.0 | 25.0 | 423 | .036 | 3.62 | 13210 |
37 | 4.45 | 19.83 | 533 | .028 | - | 16660 |
38 | 3.97 | 15.7 | 673 | .022 | 2.5 | 21010 |
39 | 3.5 | 12.47 | 848 | .018 | - | 26500 |
40 | 3.14 | 9.89 | 1070 | .014 | 1.77 | 33410 |
41 | 2.8 | 7.842 | - | - | 1.52 | - |
42 | 2.494 | 6.219 | - | - | 1.28 | - |
43 | 2.221 | 4.932 | - | - | 1.060 | - |
44 | 1.978 | 3.911 | - | - | 0.916 | - |
45 | 1.761 | 3.102 | - | - | - | - |
46 | 1.568 | 2.460 | - | - | - | - |
47 | 1.397 | 1.951 | - | - | - | - |
48 | 1.244 | 1.547 | - | - | - | - |
49 | 1.107 | 1.227 | - | - | - | - |
50 | 0.986 | 0.973 | - | - | - | - |
General Notes:
The wire size is different between the American Wire Gage [AWG] and the
British standard. The table above only lists the AWG standard.
AWG [American Wire Gauge] may also be called the Brown and Sharpe (B&S) Wire Gauge. [note]
The Birmingham Wire Gauge [BWG] is used for steel armor wire. [other wire gauge standards]
Watch for round-off errors, as many numbers were rounded. Use the table as a guide. [Equivalent Cross-Sections of Wire]
The weight [pound per foot] does not include wire insulation. The
weight of the wire is critical in some applications. More data [AWG Table for 25C - 65C]
Circular mils is the diameter squared in mils. [Table of AWG sizes in metric]
The editor has never seen the American Wire Gauge [AWG]
Current Notes: The current shown per wire size listed above is based on 1 amp/ 700 Circular mils, other tables provide different current per wire size, and different current for open air ~ check your local electrical code for the correct current capacity [Ampacity]. The 1 amp/ 700 Circular mils seems to be the most conservative, other sites provide/allow for 1 amp per 200 or 300 Circular mil. For shot wire lengths use 1A/200 Circular mil, for longer wire runs use 300 Circular mil, and for very long wire runs use the table above, 1 amp / 700 Circular mil. The current rating is listed based on permissible voltage drop and not conductor heating. The ability of a wire to carry a given amount of current is affected by a number of additional factors, which are not accounted for in the AWG table above. The ambient temperature of the surrounding air, wire insulation, and number of other wires bundled together [provided below]. Ampacity relates to the ability of the conductor to carry current [amps] before the cable over heats. I understand there are hundreds of Ampacity tables for many different conditions. The numbers above are but one example. Ampacity Tables for many conditions: |
IEEE Standard 835, IEEE Standard Power Cable Ampacity Tables
IEEE Standard 848, Procedure for the Determination of the Ampacity
Derating of Fire Protected Cables
ICEA P-54-440, NEMA Pub. No. WC 51 - Ampacities of Cables in Open-Top
Trays.
The National Electrical Code [NEC] requires their own cable sizing for
premises wiring. Refer to the NEC rules to determine building wiring, as
this page relates to electronic equipment wiring. For reference, the
ampacity of copper wire at 300C for common wire sizes
14 AWG may carry a maximum of 20 Amps in free air, or 15 Amps as part of
a 3 conductor cable.
12 AWG may carry a maximum of 25 Amps in free air, or 20 Amps as part of
a 3 conductor cable.
10 AWG may carry a maximum of 40 Amps in free air, or 30 Amps as part of
a 3 conductor cable.
8 AWG may carry a maximum of 70 Amps in free air, or 50 Amps as part of a
3 conductor cable.
The wire fusing [melting] current is based on the material the wire is
made of, the diameter of the wire and the melting point of the the
material. The wire fusing current of a wire is provided in tables as
constant current or as [a larger] current for some given amount of
time.
I found this formula used on a few different sites [un-verified];
I=Ad(3/2) @ d is in inches, A is a constant: A = 10,244 for
Copper. A = 7,585 for Aluminum.
I have listed a number of values for fusing current in the table above,
for selected AWG sizes.
Aluminum wire properties are listed under on the Aluminum electrical Wire page
Manufacturers listing for Electrical Wire and
Cable,
also Monel wire, and Nichrome wire
----------------------------------
Cable manufacturers will provide different numbers based on the
insulation used for the wire.
Use the table below to off-set the conservative current carrying numbers
in the table above, and the fusing current. The table below lists copper
wire with a Teflon [TFE] insulation. Teflon insulation has a higher
operation temperature range then other insulators, for example PVC. The
table below is based on data derived from MIL-STD-975, using
700C as the operating temperature. To derate based on number
of wires in a bundle:
IBW = ISW x (29 - #wire) / 28 @ [1 to 15
Bundled wires]
IBW = ISW x (0.5) @ [more then 15 Bundled
wires]
ISW = Single wire
IBW = Bundled wires
To derate by temperature use; derate by 80% at 1500C, 70% at
1350C, or 50% at 1050C (per MIL-STD-975)
AWG | Current Carrying | AWG | Current Carrying |
00 | 169 | 0 | 147 |
2 | 108 | 4 | 81 |
6 | 60 | 8 | 44 |
10 | 33 | 12 | 25 |
14 | 19 | 16 | 13 |
18 | 9.2 | 20 | 6.5 |
22 | 4.5 | 24 | 3.3 |
26 | 2.5 | 28 | 1.8 |
30 | 1.3 | - | - |
Refer to the How to Derate
Components page for derating wire with other then Teflon
insulation
I have seen one other Military Specification [MIL-STD-xx] for copper wire
current capability. That standard [I did not note the standard number]
listed AWG 18 [for example] as 10 amps with TFE insulation. That
indicates that this additional military specification uses the same data
listed in the table above, but may be listed for 250C, and not
700C as the table uses. So this table above has already been
derated for 700C.
This page provides a conservative guide for Ampacity for bare copper wire
[700 Circular mils/amp] , the melting [point] current for bare copper
wire, and the Ampacity for TFE coated copper wire. The American Wire Gage
[AWG] for bare copper wire is also listed. Refer to the National
Electrical Code [NEC] to determine cable sizing for premises wiring. This
page represents my notes on the subject, purchase one of the standards or
specifications referenced on this page when doing professional
work.
Also see the Wire Insulation Color Code page; Color
coding of wire insulation based on application.
Determine cable length vs. voltage drop. Determine cable length vs. Heat increase.
----------------------------------
Related technical data on Chassis Cable Design and Considerations
Technical Key words: American Wire Gage, AWG, Bare copper wire,
Ampacity, Fusing, Brown and Sharpe (B&S), Wire gauge chart
Electrical Wire Sizing,
Cable, Wiring, Heating, Wire size amperage chart, Electrical Code, Length, NEC, National Electrical
Code.
![]() |
|||||||
Home | |||||||
|
|||||||
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
Distributors | Components | Equipment | Software | Standards | Buses | Design | Reference |