Good Crimps and How to Recognize Them | ![]() |
But don't let out
a huge sigh of relief quite yet --especially if the connector you've chosen
uses a crimp termination system. While this can be one of the fastest, most
reliable and rugged termination methods, if the terminal isn't crimped onto
the wire correctly you can forget all about the hard work you put into
selecting the right connector. And, although there are 13 common crimping
problems that can reduce the reliability of your product, these problems are
easy for you to avoid with a little knowledge and advance planning.
To begin with, it
helps to understand that a terminal has three major sections: Mating,
Transition and Crimping (Illustration A). The
Mating section, as the name implies, is the section of the terminal that
mates, or becomes the interface, with the other half of the connection. This
section was designed to mate with a terminal of the opposite gender and to
perform in a certain manner by the connector design engineer. Anything that
you do that deforms the Mating Section, especially during the crimping
process, will only reduce the connector's performance.
The Transition
Section also is designed so that it would not be affected by the crimping
process. Here again, anything you do that changes the position of the Locking
Tangs or Terminal Stop affects the connector's performance.
The Crimp
Section is the only section that the crimping process is designed to affect.
Using termination equipment recommended by the connector manufacturer, the
crimp section is deformed so it can be securely attached to a wire. Ideally,
all the work that you do to crimp a terminal onto a wire occurs only in the
Crimp Section.
An example of a
properly performed crimp is seen in Illustration B. Here, the
insulation crimp compresses the insulation without piercing. The wire strands
(or brush) protrude through the front of the conductor crimp section by at
least the diameter of the wire's conductor. For example, an 18 AWG wire would
protrude at least .040". Both the insulation and conductor are visible in the
area between the insulation and the conductor Crimp Section. The conductor
Crimp Section shows a bellmouth shape in the leading and trailing ends, while
the Transition and Mating Sections remain exactly the same as they were before
the crimping process.
If your crimped
terminal does not look like the terminal in Illustration B - the
problem may have been caused by something that went wrong during the crimping
process. Here are 13 of the most common problems that may occur during the
crimping process and what you can do to avoid them.
A crimp height
that is either too small (Figure I) or too large
(Figure II)
will not provide the specified crimp strength (terminal retention to the
wire), will reduce the wire pull out force and current rating, and may
generally cause the crimp to under perform in otherwise normal operating
conditions. A crimp height that is too small also may cut strands of the wire
or fracture the metal of the conductor crimp section.
The solution to
problems #1 & #2 is very simple: adjust the conductor crimp height on the
crimp press. Using a caliper or micrometer as shown in Illustration B, verify
that the crimp height is within specification when the press is first used for
a production run and recheck it as frequently as necessary during the run to
maintain the proper crimp height.
Most types of
crimp tooling allow the insulation crimp height to be adjusted independently
of the conductor crimp height. The correct adjustment allows the terminal to
grip the insulation for at least 180 degrees without piercing the insulation.
An insulation displacement, or compression where the OD of the terminal's
insulation crimp and the OD of the insulation are approximately the same, is
ideal.
7. Wire Inserted Too Far
The third
failure mode may occur when the connectors are mated. If the wire protrudes so
far into the Transition Section that the tip of the male terminal hits against
the wire, it may prevent the connectors from fully seating or it may bend the
male or female terminals. This condition is known as "terminal
butting".
Under extreme
cases, the terminal may be pushed out the back of the housing even though it
was fully seated in the housing. To solve this problem, make certain the wire
is not inserted into the press with so much force that it overcomes the wire
stop on the press, or adjust the position of the wire stop so that it
correctly axially positions the stripped wire.
8. "Banana" (Excessive Bending) Terminal
The solution is
relatively simple. What causes the problem is that the terminal and carrier
strip (the band or strip of metal the terminals are attached to when you
receive them from the manufacturer) is not properly located with respect to
the press. To solve it, simply loosen the base plate of the interchangeable
tooling and realign it to the press.
The solution is
fairly simple. Adjust the baseplate on the press so the terminal is centered
properly in the crimp press. Another indication that the terminal is not
centered correctly is that the bellmouth isn't properly former either. This
occours because the tooling for the bellmouth and the carrier cutoff are
spatially related.
If the damage is
occurring at the crimping press, then the friction wheel needs to be adjusted
so it is only tight enough to keep the reel of terminals from being unwound by
their own weight. If the problem is occurring during the bundling process,
smaller bundles or improved handling procedures need to be implemented.
1.Choose the right connector for your application requirements.2. Use the crimp tooling specified by the terminal manufacturer.
3. Properly adjust and maintain the crimp tooling in good working order.
4. Periodically replace the parts that displace metal (e.g. conductor and insulation punches, anvils and terminal cutters).
*The parts of the crimp tooling that significantly displace the metal of the terminal - the conductor and insulation punch, anvils and the terminal cutoff tooling will need to be periodically replaced.