| Good Crimps and How to Recognize Them | ![]() |

You've made it
through all the connector catalogs, found the connector that meets all your
design criteria and is just right for your application. With the right current
rating, voltage rating, circuit size, engagement force, wire AWG capabilities,
configurations, termination method and safety features, e.g. positive locks,
fully-isolated contacts, polarization and agency certifications, it is, in
short, the perfect connector.
But don't let out
a huge sigh of relief quite yet --especially if the connector you've chosen
uses a crimp termination system. While this can be one of the fastest, most
reliable and rugged termination methods, if the terminal isn't crimped onto
the wire correctly you can forget all about the hard work you put into
selecting the right connector. And, although there are 13 common crimping
problems that can reduce the reliability of your product, these problems are
easy for you to avoid with a little knowledge and advance planning.
To begin with, it
helps to understand that a terminal has three major sections: Mating,
Transition and Crimping (Illustration A). The
Mating section, as the name implies, is the section of the terminal that
mates, or becomes the interface, with the other half of the connection. This
section was designed to mate with a terminal of the opposite gender and to
perform in a certain manner by the connector design engineer. Anything that
you do that deforms the Mating Section, especially during the crimping
process, will only reduce the connector's performance.
The Transition
Section also is designed so that it would not be affected by the crimping
process. Here again, anything you do that changes the position of the Locking
Tangs or Terminal Stop affects the connector's performance.
The Crimp
Section is the only section that the crimping process is designed to affect.
Using termination equipment recommended by the connector manufacturer, the
crimp section is deformed so it can be securely attached to a wire. Ideally,
all the work that you do to crimp a terminal onto a wire occurs only in the
Crimp Section.
An example of a
properly performed crimp is seen in Illustration B. Here, the
insulation crimp compresses the insulation without piercing. The wire strands
(or brush) protrude through the front of the conductor crimp section by at
least the diameter of the wire's conductor. For example, an 18 AWG wire would
protrude at least .040". Both the insulation and conductor are visible in the
area between the insulation and the conductor Crimp Section. The conductor
Crimp Section shows a bellmouth shape in the leading and trailing ends, while
the Transition and Mating Sections remain exactly the same as they were before
the crimping process.
If your crimped
terminal does not look like the terminal in Illustration B - the
problem may have been caused by something that went wrong during the crimping
process. Here are 13 of the most common problems that may occur during the
crimping process and what you can do to avoid them.


The crimp
height, which is the cross sectional height of the conductor Crimp Section
after it has been crimped, is the most important characteristic of a good
crimp. The connector manufacturer provides the crimp height for each wire size
for which the terminal was designed. The correct crimp height range or
tolerance for a given wire may be as small as 0.002". With a specification
this tight, verifying that the press is setup correctly is very important for
achieving a good crimp.
A crimp height
that is either too small (Figure I) or too large
(Figure II)
will not provide the specified crimp strength (terminal retention to the
wire), will reduce the wire pull out force and current rating, and may
generally cause the crimp to under perform in otherwise normal operating
conditions. A crimp height that is too small also may cut strands of the wire
or fracture the metal of the conductor crimp section.


A crimp height
that is too large will not compress the wire strands properly, causing
excessive voids in the Crimp Section because there is not enough
metal-to-metal contact between the wire strands and the metal of the
terminal.
The solution to
problems #1 & #2 is very simple: adjust the conductor crimp height on the
crimp press. Using a caliper or micrometer as shown in Illustration B, verify
that the crimp height is within specification when the press is first used for
a production run and recheck it as frequently as necessary during the run to
maintain the proper crimp height.


Connector
manufacturers do not typically supply a crimp height for the insulation due to
the variety of insulation types and thicknesses. The insulation crimp provides
a strain relief for the conductor Crimp Section so that as the wire flexes,
the wire strands do not break. An insulation crimp section that is too small
may overstress the metal in the insulation Crimp Section, weakening the strain
relief function.
Most types of
crimp tooling allow the insulation crimp height to be adjusted independently
of the conductor crimp height. The correct adjustment allows the terminal to
grip the insulation for at least 180 degrees without piercing the insulation.
An insulation displacement, or compression where the OD of the terminal's
insulation crimp and the OD of the insulation are approximately the same, is
ideal.

Loose wire strands (Figure V) are another
common cause of crimping problems. If all the wire strands are not fully
enclosed in the conductor Crimp Section, both the strength of the crimp and
the current carrying capability may be greatly reduced. To get a good crimp
you need to meet the crimp height the connector manufacturer specifies. If all
the strands are not contributing to that crimp height and therefore, crimp
strength, then the crimp will not perform to specifications. Generally, the
problem of loose wire strands is very easy to solve by simply gathering the
wires back into a bunch before inserting them into the terminal to be crimped.
The strands may have been inadvertently separated during the handling or
bundling process if stripping the insulation from the wire is done as a
separate operation. Using a "strip and retain" process for insulaton removal,
where the insulation slug is not completely removed from the wire until it is
ready to have a terminal crimped onto the wire, helps minimize the
problem.

If the strip
length is too short or if a wire is not fully inserted into the conductor
Crimp Section, the termination may not meet the specified pull force because
the metal-to-metal contact between the wire and the terminal is reduced. As
shown in Figure
VI, the strip length of the wire is too short (note that the
insulation is in its proper position), not allowing the required one wire OD
extension in front of the conductor Crimp Section. The solution is simple:
increase the strip length of the wire stripping equipment to that specified
for that specific terminal.

7. Wire Inserted Too Far
Another crimping
problem that relates to a too short strip length occurs when the wire is
inserted too far into the crimp sections. As Figure VII shows, the
insulation is too far forward of the insulation Crimp Section and the
conductors protrude into the Transition Section. This may cause as many as
three failure modes in the actual application. Two relate to a reduced current
rating/wire pull out force due to a reduction of the metal-to- metal contact
in the conductor Crimp Section. A metal-to-plastic contact isn't as strong,
nor does it conduct electricity, as well as metal-to-metal.
The third
failure mode may occur when the connectors are mated. If the wire protrudes so
far into the Transition Section that the tip of the male terminal hits against
the wire, it may prevent the connectors from fully seating or it may bend the
male or female terminals. This condition is known as "terminal
butting".
Under extreme
cases, the terminal may be pushed out the back of the housing even though it
was fully seated in the housing. To solve this problem, make certain the wire
is not inserted into the press with so much force that it overcomes the wire
stop on the press, or adjust the position of the wire stop so that it
correctly axially positions the stripped wire.
8. "Banana" (Excessive Bending) Terminal
One of the most
descriptive crimping problems is known as a "banana" crimp (Figure VIII), because
the crimped terminal takes on a banana shape. This makes it difficult to
insert the terminal into the housing and may cause terminal butting. This
problem is easy to solve by adjusting the position of the hold down pin on the
crimp press. This small pin is located in the crimp press and contacts the
terminal in the mating section while the crimp sections are being crimped onto
the wire. During crimping, a significant amount of metal on one end of the
terminal (in the crimp section) moves. These high forces tend to force the
front of the terminal upwards, unless it is held down by the aptly-named
"holddown pin".
One of the more
obvious crimping problems is when part of the Transition Section is damaged,
as shown in Figure
IX. In the terminal shown, the tab sticking up is a design
feature called a "terminal stop". Its function is to prevent the terminal from
being inserted too deeply into the housing. If the stop is extremely damaged,
the terminal can actually be pushed all the way through the housing.
The solution is
relatively simple. What causes the problem is that the terminal and carrier
strip (the band or strip of metal the terminals are attached to when you
receive them from the manufacturer) is not properly located with respect to
the press. To solve it, simply loosen the base plate of the interchangeable
tooling and realign it to the press.
The correct size
for a bellmouth (Figure
X) is approximately 2X the thickness of the terminal material.
For example if the terminal is made from material that is .008" thick, the
bellmouth should be approximately .016". While a few thousands of an inch
either way will not materially affect the terminal's performance, if the
bellmouth is missing or if it is less than one material thickness, there is a
risk of cutting the wire strands. The fewer strands that remain, the lower the
termination strength. To correct the problem, make sure the punch and anvil on
the crimping equipment are properly aligned.
There is also a
problem if the bellmouth is oversized (Figure Xl), because
this reduces the total area that the crimp section of the terminal has in
contact with the wire. The less the wire-to-terminal interface, the lower the
wire pull out force. If the crimp height is correct, then it is likely the
problem is caused by worn tooling, which should be replaced.
The carrier
strip is cut off of the terminal during the crimping process. If the remaining
cutoff is too long (Figure XII), problems
can occur. The extra metal may protrude out the rear of the connector when the
terminal is inserted into the housing, causing the connector to arc between
adjacent contacts when higher voltages are applied. If the carrier cutoff at
the front of the terminal is too long, the extra length may interfere with
connector mating and result in "terminal butting".
The solution is
fairly simple. Adjust the baseplate on the press so the terminal is centered
properly in the crimp press. Another indication that the terminal is not
centered correctly is that the bellmouth isn't properly former either. This
occours because the tooling for the bellmouth and the carrier cutoff are
spatially related.

Although bent
lock tangs are not necessarily the result of a poor crimping process, the
connector can fail just the same. Lock tangs (Figure XIII may be
bent either in or out too far, which impacts the terminal's ability to
completely lock into the shelf in the housing that was designed for this
purpose. The tangs may be damaged as the terminals are unwound from the reel
if the friction wheel on the reel holder of the crimp press is too tight or it
can be caused by handling after the terminals are crimped onto the wires.
Typically, terminated wires are gathered into a bundle and inventoried or
transported to another location in the plant. During the bundling, or as each
terminated wire is removed from the bundle, the locking tangs may be
bent.
If the damage is
occurring at the crimping press, then the friction wheel needs to be adjusted
so it is only tight enough to keep the reel of terminals from being unwound by
their own weight. If the problem is occurring during the bundling process,
smaller bundles or improved handling procedures need to be implemented.
While there are
13 problems that may be caused during the crimping process, there are just
four simple rules that will help ensure a successful connector
application:
1.Choose the right connector for your application requirements.2. Use the crimp tooling specified by the terminal manufacturer.
3. Properly adjust and maintain the crimp tooling in good working order.
4. Periodically replace the parts that displace metal (e.g. conductor and insulation punches, anvils and terminal cutters).
Since most of the problems that
are reported to connector manufacturers relate to one of these thirteen
crimping problems, Molex offers an easy-to-use guide to help you avoid
problems or recognize them quickly enough so that you make only good crimps.
To order this guide contact Molex Incorporated, 2222 Wellington Court, Lisle,
Illinois 60532, Attention: Good Crimp Drawings.
*The parts of the crimp tooling that significantly displace the metal of the terminal - the conductor and insulation punch, anvils and the terminal cutoff tooling will need to be periodically replaced.